Server Technology Solutions for the Data Center Equipment Cabinet Sentry Remote Power Manager - PT22 Installation and Operations Manual © 2005
Interfaces The PT22 has two interfaces: the HTML interface accessed via the HTTP enabled Ethernet connections and the command line for serial and Teln
HTML Interface The HTML interface is constructed of three major components: the System Location bar, the User/Navigation bar and the Control Screen.
Outlet Control The Outlet Control section offers access to the Individual and Group outlet control pages. From the Individual and Group pages, the us
Environmental Monitoring Input Load The Input Load page displays the tower(s) absolute and descriptive name and the cumulative input load in amperes o
Network The Network configuration page is used for maintenance of the network interface. From this page an administrator may configure the IP address
Setting SSL access level Sentry SSL supports configuration of SSL connections as being either optional or required. The default access level is set t
Editing modem initialization strings: Click on the Edit link in the Modem port Action column. On the subsequent Serial Port Edit page, enter the initi
Adding and Deleting outlets from a group: Press the Edit link in the Action column for the associated group. On the subsequent Group Edit page, sele
Adding and Deleting serial port access: Click on the Ports link in the Access column for the associated user. On the subsequent User Ports page, sel
Configuring input feed traps: Click on the Input Feed Traps link. On the subsequent Input Feed Traps page, select or deselect the desired traps and pr
Instructions This symbol is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literatu
Configuring the authentication order: Select Remote -> Local or Remote Only from the drop-down menu and press Apply. For more information on remote
Configuring the authentication order: Select Remote -> Local or Remote Only from the drop-down menu and press Apply. For more information on remote
Command Line Interface Logging In Logging in through Telnet requires directing the Telnet client to the configured IP address of the unit. Logging in
Administrative Command Summary (continued) Delete Portfromuser Removes access to one or all serial ports List User Displays all accessible outlets/g
Operations Commands Operations commands manage outlet states, provide information about the Sentry environment and control session operations. Turning
Displaying outlet status The Status command displays the on/off status of one or more outlets. The command displays the status of only those outlets
Displaying accessible outlets The List Outlets command displays accessible outlets for the current user. The display includes the absolute and descri
Displaying infeed status The Istat or Iload command displays the status of one or more infeed. This display includes the infeed absolute and descript
Ending a session The Quit or Logout commands ends a session. A session ends automatically when no activity is detected for five minutes, or upon loss
Examples The following command changes the password for the user JohnDoe: Sentry: set user password johndoe<Enter> Password: <Enter>
Table of Contents CHAPTER 1: INTRODUCTION 4 Quick Start Guide...
Adding outlet access to a user The Add OutletToUser command grants a user access to one or all outlets. To grant access for more than one outlet, bu
Deleting serial port access for a user The Delete PortFromUser command removes a user’s access to a serial port. You cannot remove access to any seria
Creating a descriptive outlet name The Set Outlet Name command assigns a descriptive name to an outlet. You may use this name in commands that requir
Displaying outlet information The Show Outlets command displays information about all outlets. This information includes: • Sequencing and reboot t
The following commands usese the outlets’ descriptive names to add outlets DataServer_1 and WebServer_1 to group name ServerGroup_1: Sentry:add Outlet
Setting the serial ports data-rate The Set Port Speed command sets the default data-rate for the serial port. Valid data-rates are 1200, 2400, 4800
Editing modem initialization strings The predefined modem initialization strings may be edited by an administrative user. The Init 1 and Init 2 strin
System Administration Creating a location description The Set Location command specifies text that appears in the HTML control screen’s Location field
Displaying tower information The Show Towers command displays information about the Sentry. This information includes the absolute and descriptive Se
TCP/IP Administration NOTE: A restart of the Sentry is required after setting or changing ANY TCP/IP configurations. See Performing a warm boot on p
Chapter 1: Introduction Quick Start Guide The following instructions will help you quickly install and configure your PT22 for use in your data cent
Displaying network configuration information The Show Network command displays TCP/IP, Telnet, SSH, Web, SSL and SNMP configuration information. • I
Telnet Administration NOTE: A restart of the Sentry is required after setting or changing ANY Telnet/Web configurations. See Performing a warm boot
Setting the filename to be uploaded The FTP Filename command sets the filename of the firmware file to be uploaded. To set the FTP filename: At the Se
Displaying SNTP configuration information The Show SNTP command displays all SNTP configuration information. To display SNTP configuration information
Chapter 4: Advanced Operations SSL 46 Enabling and Setting up SSL Support 46 SSL Technical Specifications 46 SSH 47 Enabling and Setting up SSH Supp
SSL Secure Socket Layers (SSL) version 3 enables secure HTML sessions between a Sentry Remote Power Manager and a remote user. SSL provides two chief
SSH Secure Shell (SSH) version 2 enables secure network terminal sessions between a Sentry Remote Power Manager and a remote user over insecure networ
SNMP The Sentry family of products supports the Simple Network Management Protocol (SNMP). This allows network management systems to use SNMP request
Setting the trap timer The Set Traptime command sets the timer period between repeated error-condition traps. The valid range for the timer period is
Equipment Overview 1. The power inlet/cord(s) connects the CDU to the electrical power source. 2. Two RJ45 connectors for Serial (RS-232) and Ethern
SNMP Traps The Sentry supports three types of SNMP traps. Traps are enabled at the tower (T), infeed (I) or outlet (O) level. Trap Summary Name Level
Load Trap The Load trap is generated whenever the total input load on an infeed exceeds a preset threshold. Load traps include the reported input loa
Enabling or Disabling a Load trap The Set Trap Infeed Load command is used to enable or disable an Infeed Load trap. To Enable or Disable a Load trap:
Displaying trap configuration information The Show Traps command displays information about all traps. To display trap information: At the Sentry: p
LDAP The Sentry family of products supports Lightweight Directory Access Protocol (LDAP) Version 3. This support enables authentication with LDAP se
Enabling and Setting up LDAP Support There are a few configuration requirements for properly enabling and setting up LDAP support. Below is an overvi
Setting the search bind Distinguished Name (DN) The Set LDAP BindDN command is used to set the fully-qualified distinguished name (FQDN) for user acco
Setting the user search base Distinguished Name (DN) The Set LDAP UserBaseDN command is used to set the base (DN) for the login username search. This
Displaying LDAP configuration information The Show LDAP command displays LDAP configuration information. • Enabled-disabled status of LDAP support •
Configuring LDAP Groups Creating an LDAP group The Create LDAPGroup command creates an LDAP group. To create an LDAP group: At the Sentry: prompt, typ
Chapter 2: Installation Before installing your Sentry PT22, refer to the following lists to ensure that you have all the items shipped with the unit a
Displaying the LDAP access privilege levels The List LDAPGroups command displays all defined LDAP group with their access privilege level. To display
Adding serial port access to an LDAP group The Add PortToLDAP command grants an LDAP group access to the serial port. To grant serial port access to
LDAP Technical Specifications 62 • Advanced Operations Sentry PT22 Simple Bind Authentication ProcessLDAP Server SentryClientInitiate Sentr
TACACS+ The Sentry family of products supports the Terminal Access Controller Access Control System (TACACS+) protocol. This enables authentication
Setting the TACACS+ encryption key The Set TACACS Key command sets the encryption key used to encrypt all data packets between the Sentry and the TACA
Configuring TACACS+ Privilege Levels Setting TACACS+ account access level privileges The Set TacPriv Access command sets the access level privileges f
Deleting outlet access for a TACACS+ account The Delete OutletFromTACACS command removes a TACACS+ account’s access to one or all outlets. You canno
Displaying outlet, outlet group and serial port access The List TacPriv command displays all accessible outlets, outlet groups and serial ports for a
Chapter 5: Appendices Appendix A: Resetting to Factory Defaults You may reset the non-volatile RAM that stores all configurable options. This clears
Appendix C: Technical Specifications Domestic Models Model Voltage Inlets* Outlets PT22-H004-1-02 100-120V, 50/60Hz 4 x IEC 60320 C20 4 x IEC 6
Mounting 1. Select the appropriate bracket mounting points for proper mounting depth within the rack. 2. Attach the brackets to these mounting point
Data Connections RS-232 port PT22s are equipped standard with an RJ45 DTE RS-232c serial port. This connector may be used for direct local access or
Regulatory Compliance Product Safety Units have been safety tested and certified to the following standards: • USA/Canada UL 508 and CAN/CSA 22.2
Appendix D: Warranty, Product Registration and Support Warranty and Limitation of Liability Server Technology, Inc. agrees to repair or replace Produ
Technical Support Server Technology understands that there are often questions when installing and/or using a new product. Free Technical Support is